Typical application wiring, connection of terminals
Info mode
If in doubt of setting of installed transmitter, verification of its address is enabled even
without using computer. Power should be connected.
Unscrew transmitter cover and shortly press button next to connection terminals (jumper
should be opened). Actual adjusted address of transmitter is displayed on LCD display at decimal
base. Next press of button exits info mode and actual measured values are displayed.
Note: No measurement and communication is possible during info mode. If transmitter stays in info
mode for longer than 15 s, transmitter automatically returns to measuring cycle.
Description of communication protocols
Detailed description of each communication protocols including examples of
communication is available in individual document “Description of communication protocols of
Txxxx series”.
Note: After switching ON the power of the device it can last up to 2 s before the device starts to
communicate and measure!
Modbus RTU
Control units communicate on master-slave principle in half-duplex operation. Only master
can send request and only addressed device responds. During sending of request no other slave
station should respond. During communication, data transfer proceeds in binary format. Each Byte
is sent as eight bit data word in format: 1 start bit, data word 8 bit (LSB first), 2 stop bits
1
, without
parity. Transmitter supports communication speed from 110Bd to 115200Bd.
4
1
Transmitter sends two stop bits, for receive one stop bit is enough.